Amperage Chart

Current carrying capacity is defined as the amperage a conductor can carry before melting either the conductor or the Insulation. Heat, caused by an electrical current flowing through the conductor, will determine the amount of current a wire will handle. Theoretically, the amount of current that can be passed through a single bare copper wire can be increased until the heat generated reaches the melting temperature of the copper. There are many factors which will limit the amount of current that can be passed through a wire. These major determining factors are:

Conductor Size: The larger the circular mil area, the greater the current carrying capacity. The amount of heat generated should never exceed the maximum Temperature Rating of the Insulation.

Ambient Temperature: The higher the Ambient Temperature, the less heat required to reach the maximum temperature rating of the Insulation.

Conductor Number: Heat dissipation is lessened as the number of individually insulated conductors, bundled together, is increased.

Installation Conductors: Restricting the heat dissipation by installing the conductors in Conduit, Duct, trays or raceways lessens the current carrying capacity. This restriction can be alleviated somewhat by using proper ventilation methods, forced air cooling, etc. Taking into account all the variables involved, no simple chart of current ratings can be developed and used as the final word when designing a system where amperage ratings can become critical.The chart shows the current required to raise the temperatures of single insulated conductor in free air (30°C ambient) to the limits of various Insulation types. The following table gives a Derating Factor to be used when the conductors are bundled. These charts should only be used as a guide when attempting to establish current ratings on conductor and cable.


DERATING FACTORS FOR BUNDLED CONDUCTORS
BUNDLE # DERATING
FACTOR (X AMPS)
2-5 0.8
6-15 0.7
16-30 0.5

CURRENT CARRYING CAPACITY OF COPPER CONDUCTORS (Measured in Amperes)
CONDUCTOR
SIZE
INSULATION MATERIALS AT GIVEN TEMPERATURES
POLYETHYLENE
NEOPRENE
POLYURETHANE
POLYVINYL-
CHLORIDE
(SEMI-RIGID)
AT 80
º C
POLY-
PROPYLENE
POLYETHYLENE
(HIGH DENSITY)
AT 90
º C
POLYVINYL-
CHLORIDE
PVC (IRRADIATED)
NYLON
AT 105
º C
Kynar
POLYETHYLENE
(CROSSLINKED)
Thermoplastic
Elastomer S
AT 125
º C
Polyimide Resin
FEP-TFE
SILICONE
AT 200
º C
30 AWG 2 3 3 3 4
28 AWG 3 4 4 5 6
26 AWG 4 5 5 6 7
24 AWG 6 7 7 8 10
22 AWG 8 9 10 11 13
20 AWG 10 12 13 14 17
18 AWG 15 17 18 20 24
16 AWG 19 22 24 26 32
14 AWG 27 30 33 40 45
12 AWG 36 40 45 50 55
10 AWG 47 55 58 70 75
8 AWG 65 70 75 90 100
6 AWG 95 100 105 125 135
4 AWG 125 135 145 170 180
2 AWG 170 180 200 225 240



Return to Technical Information | Products

PRODUCTS

FEP-TFE-PTFE-Wire
ETFE-XLETFE Wire
MIL-W-22759 Wire
MIL-W-16878 Wire
MIL-W-81044 PVF Wire
MIL-W-81381 Polyimide Resin Wire
MIL-W-5086A, Type 1 & 2
FEP-TFE Shielded Cable
ETFE-XLETFE Shielded Cable
MIL-C-27500 Cable
PVC and XLPE Wire
Silicone Wire
Automotive Wire
Marine Wire & Cable
High Temp Wire
High Voltage Wire
FEP-TFE Flat Ribbon Cable
PVC Instrumentation Cable

Belden Equivalent
FEP Plenum Cables
Up to 50% Savings

Custom Designed
Cable and Wire

PVC Direct Burial Cable
Coax Cable
Copper Braid
Heatshrink & Sleeving
Braided Poly Sleeving
Braided FEP-TFE Sleeving